The K-factor of a nozzle is the constant that links its flow rate to the pressure: Q = K × √P. With flow in l/min and pressure in bar, K is expressed in (l/min)/√bar and is obtained by dividing a catalogue flow rate by the square root of the pressure at which it was measured.
Example: a nozzle that delivers 25 l/min at 3 bar has K = 25 ÷ √3 = 14.43. The higher the K, the more flow at the same pressure; and to double the flow of a nozzle you have to multiply the pressure by four.
The K-factor formula: Q = K × √P
A nozzle is, hydraulically, a calibrated orifice. The speed of the water passing through it increases with the square root of the pressure, and that gives the relationship we use across the whole catalogue:
The other three forms you will need are simple rearrangements of the same equation:
Use the calculator to solve for K, flow or pressure in metric (l/min, bar) or imperial (GPM, psi) units. If you also need the effect of pressure on droplet size or spray pattern, it is explained in the guide to pressure and flow in spray nozzles.
K-factor calculator
Calculate flow, pressure or K-factor for spray, atomising, industrial washing and misting nozzles.
Q is the flow rate, K is the nozzle coefficient and P is the working pressure.
Worked example: from the data sheet to the real flow rate
1. Work out K: √3 = 1.732 → K = 25 ÷ 1.732 = 14.43.
2. Flow at 5 bar: Q = 14.43 × √5 = 14.43 × 2.236 = 32.3 l/min.
3. Pressure for 20 l/min: P = (20 ÷ 14.43)² = 1.386² = 1.92 bar.
Check: 25 × √(5 ÷ 3) = 32.3 l/min. Same result without calculating K.
K-factor of the BOCASPER range: real data-sheet values
This table lists the flow rate published on each nozzle’s data sheet and the resulting K-factor (or the one given by the sheet itself, as with the FA-01 sprinkler). All values are for water. Click the reference to see the full product page, with its pressure range and price.
| Ref. | Type | Material · thread | Flow (l/min) | Pressure (bar) | K-factor |
|---|---|---|---|---|---|
| CA-07 | Water curtain 70° | Brass · M-12 | 4.5 | 3 | 2.60 |
| CA-14 | Water curtain 70° | Brass · 1/4″ BSPT | 4.5 | 3 | 2.60 |
| CA-20 | Water curtain 70° | POM · 3/8″ BSPT | 6 | 3 | 3.46 |
| CR-02 | Side curtain 160° | Brass · 1/4″ BSPT female | 11 | 3 | 6.35 |
| FC-02 | Flat fan 80° | AISI 303 | 12.5 | 3 | 7.22 |
| FA-01 | Fire sprinkler | Chrome-plated brass · 1/2″ BSPT | 30 | 3.5 | 16 |
| CA-04 | Water curtain 70° | Brass · 1/4″ BSPT | 25 | 3 | 14.43 |
| CA-08 | Water curtain 70° | Brass · M-12 | 25 | 3 | 14.43 |
| WA-30 | Duckbill 145° | Aluminium · 1 1/2″ BSPT | 40 | 3 | 23.09 |
| EA-40 | Straight jet | Stainless 303 · 3/8″ BSPT | 43.2 | 3 | 24.94 |
| BA-11 | Full cone 60° | Delrin · 1″ BSPT | 60 | 3 | 34.64 |
If you are looking for a nozzle by flow rate, go straight to the categories of water curtains and flat fan, full cone, solid jets and fire sprinklers.
What flow does a nozzle give when the pressure changes
With the K-factor from the table above you can anticipate consumption at any pressure. These are the flow rates (l/min) of three real nozzles calculated with the formula:
| Nozzle | 1 bar | 2 bar | 3 bar | 5 bar | 7 bar | 10 bar |
|---|---|---|---|---|---|---|
| CA-14 / CA-07 K = 2.60 | 2.6 | 3.7 | 4.5 | 5.8 | 6.9 | 8.2 |
| CA-08 / CA-04 K = 14.43 | 14.4 | 20.4 | 25.0 | 32.3 | 38.2 | 45.6 |
| EA-40 K = 24.94 | 24.9 | 35.3 | 43.2 | 55.8 | 66.0 | 78.9 |
Two quick rules that follow from the table: if you double the pressure the flow only rises 41%, and if you quadruple it the flow doubles. If you need much more flow, it is usually better to choose a nozzle with a higher K than to push the pump.
K-factor and orifice size
The K-factor depends mainly on the area of the orifice. Applying the flow equation through an orifice with water, for a circular orifice of diameter d (in mm) we get:
Because the diameter is squared, doubling the diameter multiplies the K-factor by four. The discharge coefficient Cd depends on the internal geometry (chamber, swirl, slot) and is set by the manufacturer; it cannot be deduced from the diameter alone. By way of illustration, with Cd = 0.6 (a typical value for a sharp-edged orifice):
| Orifice diameter | Theoretical K-factor |
|---|---|
| 1 mm | 0.40 |
| 2 mm | 1.60 |
| 4 mm | 6.40 |
In flat fan nozzles, such as the FC-02 (2.3 mm slot), K depends on the slot and the internal chamber, not on a single diameter. For a specific reference, rely on the flow rate on the data sheet, not on the apparent size of the orifice.
K-factor in l/min·bar and in GPM·psi
The K-factor carries the units of the flow and pressure used to calculate it. American manufacturers give it in GPM/√psi; in Europe (l/min)/√bar is used. To convert from one to the other:
| K (GPM/√psi) | K ((l/min)/√bar) |
|---|---|
| 2.8 | 40.4 |
| 5.6 | 80.7 |
| 8.0 | 115.3 |
| 11.2 | 161.5 |
| 14.0 | 201.8 |
The FA-01 sprinkler has K = 16 in metric units, equivalent to 1.11 GPM/√psi. Before comparing nozzles from different manufacturers, check which units the K-factor is given in.
When the formula falls short
- K is not perfectly constant. The CA-04 data sheet gives 13.5 l/min at 1 bar, 25 at 3 bar and 45 at 10 bar, which gives K = 13.50, 14.43 and 14.23: a variation of about 6%. For pressures far from the nominal one, use the flow table on the data sheet.
- Liquid density. The published K is for water. For a liquid with relative density SG, the flow is the water flow divided by √SG: with SG = 1.2, a 25 l/min nozzle drops to 22.8 l/min.
- The pressure is the nozzle’s, not the pump’s. Filters, elbows, long pipes and valves take pressure away before it reaches the orifice.
- Wear and blockage. A worn orifice increases the real K; a blocked one reduces it. If the flow changes at the same pressure, inspect the nozzle.
- It does not apply to compressed air or air + water. Air is compressible and air-atomising or air blow-off nozzles do not follow Q = K × √P with a single factor.
| Pressure | Data-sheet flow (l/min) | Calculated K |
|---|---|---|
| 1 bar | 13.5 | 13.50 |
| 3 bar | 25.0 | 14.43 |
| 10 bar | 45.0 | 14.23 |
How to choose a nozzle using the K-factor
- Define the flow per nozzle: total available flow ÷ number of active nozzles.
- Find the real pressure at the nozzle (not the pump’s), allowing for pressure losses.
- Calculate the K you need: K = Q ÷ √P.
- Look in the catalogue for a close K and check angle, pattern, material, thread and pressure range.
- Check the total flow with the chosen nozzle: total Q = K × √P × number of nozzles.
Flow per nozzle: 120 ÷ 8 = 15 l/min. Required K: 15 ÷ √4 = 7.5.
The FC-02 (K = 7.22) gives 7.22 × 2 = 14.4 l/min at 4 bar; the 8 add up to 115.5 l/min, within the pump’s capacity.
To size the pump and pipework as well, follow the guide on how to size a spray nozzle installation.
Where the K-factor is used
- Water curtains and barriers: splitting the flow among several nozzles to cover a given width. See the water curtains.
- Industrial washing and cleaning: setting the consumption per washing point with solid jets and tank washing heads.
- Cooling, humidification and dust control: with full cone, hollow cone and fine spray nozzles, where K sets the water consumption of the whole installation.
- Fire protection: K defines the flow of each sprinkler at the available pressure; see the BOCASPER sprinklers. The design of a real installation must be carried out by a competent engineer in line with the applicable regulations.
- Irrigation and agriculture: balancing the flow per nozzle on spray booms. More at how many nozzles a spray bar needs.
Guidance tool. The calculations are approximate and valid for water. Before sizing an installation, check the result against the flow table on the data sheet of the chosen nozzle.
Frequently asked questions about the K-factor
What is the K-factor of a nozzle?
The K-factor of a nozzle is the constant that links its flow rate to the working pressure through the formula Q = K × √P. It depends on the size and geometry of the orifice: the higher the K, the more flow passes through the nozzle at the same pressure.
What is the K-factor formula?
K = Q ÷ √P, where Q is the flow in l/min and P the pressure in bar measured at the nozzle. If a nozzle gives 25 l/min at 3 bar, its K-factor is 25 ÷ √3 = 14.43 (l/min)/√bar.
What units is the K-factor expressed in?
In the metric system it is expressed in (l/min)/√bar, and in the imperial system in GPM/√psi. They are not interchangeable: to go from GPM/√psi to (l/min)/√bar you have to multiply by 14.42.
How do you calculate a nozzle’s flow rate with the K-factor?
With Q = K × √P. A nozzle with K = 14.43 working at 5 bar gives 14.43 × √5 = 32.3 l/min. If you only know a catalogue flow at another pressure, use Q₂ = Q₁ × √(P₂ ÷ P₁).
How do you calculate the pressure needed for a given flow rate?
By solving for the pressure: P = (Q ÷ K)². To obtain 20 l/min with a nozzle of K = 14.43 you need (20 ÷ 14.43)² = 1.92 bar at the nozzle itself.
If I double the pressure, does the flow double?
No. The flow grows with the square root of the pressure: when you double the pressure the flow increases by only 41% (×1.41). To double the flow of the same nozzle you have to multiply the pressure by four.
What is the relationship between the K-factor and the orifice diameter?
The flow is proportional to the area of the orifice, and the area grows with the square of the diameter. So, with the same geometry, doubling the diameter multiplies the K-factor by four. The exact discharge coefficient of each nozzle is determined by the manufacturer.
How do I convert the K-factor from GPM/√psi to l/min/√bar?
Multiply by 14.42 (exactly 14.416: 3.7854 l per gallon divided by the square root of 0.06895 bar per psi). A K of 5.6 GPM/√psi is equivalent to about 80.7 (l/min)/√bar; in fire sprinklers it is commercially called K80.
Does the K-factor work for any liquid and any nozzle?
The published K refers to water. With a denser liquid the flow drops in proportion to 1/√(relative density): with a relative density of 1.2, a nozzle that gives 25 l/min of water gives about 22.8 l/min. In addition, the formula is not valid for compressed-air or air-atomising (air + water) nozzles, because air is compressible.